Author: Holger Stork, Achim Gaedke
|
||
Created: January 2005
|
||
|
||
****************************************************************************/
|
||
|
||
#ifndef EUROTHERM2000SERIES_H
|
||
#define EUROTHERM2000SERIES_H
|
||
|
||
#include <string>
|
||
#include <map>
|
||
#include "drivers/tempcont.h"
|
||
|
||
/**
|
||
\defgroup eurotherm2000series Eurotherm 2000 Series
|
||
\ingroup drivers
|
||
\brief remote control over serial interface
|
||
|
||
Wiring the serial interface is explained in Series 2000 Communications Handbook, Chapter 2.7.
|
||
This handbook is online available at http://www.eurotherm.com/comms/instcom.htm
|
||
The implemented EI-Bisync Protocol is described in caphter 4, the used parameter names are taken from Chapter 5
|
||
|
||
@{
|
||
*/
|
||
|
||
/**
|
||
special exception for Eurotherm 2000 drivers
|
||
*/
|
||
class Eurotherm2000Series_error: public tempcont_error
|
||
{
|
||
public:
|
||
explicit Eurotherm2000Series_error(const std::string& msg) throw (): tempcont_error(msg) {}
|
||
explicit Eurotherm2000Series_error(const char* msg) throw (): tempcont_error(msg) {}
|
||
virtual ~Eurotherm2000Series_error() throw () {}
|
||
protected:
|
||
virtual const std::string prefix() const { return "ERROR (Eurotherm2000Series_error): "; }
|
||
};
|
||
|
||
/**
|
||
this class communicates with Eurotherm 2200 Series temperature controlers
|
||
the contolers must be set to a known address, the serial line uses 19200baud, 7bit characters and even parity
|
||
there are various timeouts, that are hardcoded to detect transmition failures
|
||
*/
|
||
|
||
class Eurotherm2000Series: public tempcont
|
||
{
|
||
private:
|
||
/**
|
||
file descriptor for serial device with Eurotherm controler
|
||
*/
|
||
int serial_dev;
|
||
/**
|
||
device address, which must be set in Eurotherm device
|
||
*/
|
||
int address;
|
||
/**
|
||
serial device name
|
||
*/
|
||
std::string device_name;
|
||
/**
|
||
mask defining severe failures (abort of program could be triggered)
|
||
*/
|
||
int failure_mask;
|
||
/**
|
||
all these strange data formats of Bisynch: float values
|
||
*/
|
||
std::string fp_format;
|
||
/**
|
||
all these strange data formats of Bisynch: integer values with dot!
|
||
*/
|
||
std::string int_format;
|
||
/**
|
||
all these strange data formats of Bisynch: hexadecimal values
|
||
*/
|
||
std::string hex_format;
|
||
public:
|
||
/**
|
||
reads a value from Eurotherm
|
||
*/
|
||
void read_value(const std::string& param_name, std::string& return_value) const;
|
||
|
||
/**
|
||
sends a value to Eurotherm
|
||
*/
|
||
int set_value(const std::string& param_name, const std::string& value);
|
||
|
||
/**
|
||
send a list of configuration commands to eurotherm, make sure, that nobody uses eurotherm when calling this function
|
||
the configuration time is quite long (5 to 10 seconds) because of full device reset
|
||
*/
|
||
void configure(const std::map<std::string, std::string>& config);
|
||
|
||
void reset();
|
||
|
||
public:
|
||
/**
|
||
\brief initialise serial interface, test device communication, configure eurotherm
|
||
\param dev_name absolute path name of serial device used for communication
|
||
\param dev_address of Eurotherm device (to be set manualy in Eurotherm configuration)
|
||
\param failure_status_mask mask for status sumary to detect failures, see get_summary_status method
|
||
|
||
sets up the communication, configures Eurotherm2000 to <20>K and nnn.n display format, tests the sensor and starts temperature history
|
||
*/
|
||
Eurotherm2000Series(const std::string& dev_name = std::string("/dev/ttyS0"), int dev_address = 1, int failure_status_mask = 32);
|
||
|
||
/**
|
||
*/
|
||
virtual ~Eurotherm2000Series();
|
||
|
||
/**
|
||
get the actual temperature
|
||
*/
|
||
virtual double get_temperature() const;
|
||
|
||
/**
|
||
set temperature setpoint value
|
||
\return temperature, that is set
|
||
*/
|
||
virtual double set_setpoint(double temperature);
|
||
|
||
/**
|
||
get temperature setpoint value
|
||
\return temperature, that is set
|
||
*/
|
||
virtual double get_setpoint() const;
|
||
|
||
/**
|
||
returns summary for eurotherm as hexadecimal value
|
||
|
||
the bits meanings are:
|
||
0: Alarm 1 State
|
||
1: Alarm 2 State
|
||
2: Alarm 3 State
|
||
3: Alarm 4 State
|
||
|
||
4: Manual Mode
|
||
5: Sensor Break
|
||
6: Loop Break
|
||
7: Heater Fail
|
||
|
||
8: Load Fail
|
||
9: Ramp/Program Complete
|
||
10: Process Variable out of Range
|
||
11: SSR Fail
|
||
|
||
12: New Alarm
|
||
13: Remote Input Sensor Break
|
||
*/
|
||
virtual int get_summary_status() const;
|
||
|
||
/**
|
||
get the low and high limits for setpoints
|
||
*/
|
||
virtual void get_setpoint_limits(double& min, double& max) const;
|
||
};
|
||
|
||
/**
|
||
@}
|
||
*/
|
||